• Custom microprocessor controlled for highest accuracy and reliability.
• 3 LEDs for checking correct wiring status.
• 0 and 180 degree phase angle switch permits quick tests and consistent readings.
• Digital read-out of tripping time.
• Constant current source circuitry ensures that a fluctuating mains voltage does not affect the accuracy of readings.
• Large custom digital display readout.
• Visual indication of reversed phase and neutral wiring at socket.
• Designed to IP54 Rating.
• Complies with IEC 61557
• Test of a large kind of RCD's: Standard, Selective, AC and A (DC sensitive breakers)

• Measurement of RCD trip time
• Measurement of trip out current
• Remote Test
• Voltage Measurement
• Auto-detection of Contact voltage
• Dust- and Water-proof
• Backlight

• Custom microprocessor controlled for highest accuracy and reliability.
• 3 LEDs for checking correct wiring status.
• 15mA LOOP measurement
• Direct reading of Prospective Short Circuit Current (PSC).
• Safe voltage measurement function.
• Large custom digital display readout on all models.
• Measure low loop resistances(resolution of 0.01Ω)
• Automatic lock-out if test resister overheats.
• Large custom digital display readout.
• Visual indication of reversed phase and neutral wiring at socket.
• Designed to IP54 Rating
• Complies with IEC 61557

Anti-Trip Technology "ATT"
No RCDs tripping during Loop Testing!

The KEW 6201A is a portable appliance tester, performing four functions to ensure the Safety of ClassI and ClassII appliances. And also can measure the mains voltage.
Readings are displayed on a large liquid crystal display (LCD) below which are four LEDs which unambiguously display a pass or fail indication for threshold values dictated by AS/NZS 3760.

| Insulation resistance | PV insulation | Insulation | ||||
|---|---|---|---|---|---|---|
| Test voltage | 500V | 1000V | 250V | 500V | 1000V | |
| Measuring range(Auto range) | 20.00/200.0/2000MΩ | 20.00/200.0/2000MΩ | ||||
| Mid-scale value | ― | 50MΩ | ||||
| Rated current | ― | 1.0-1.2mA | ||||
| 0.25MΩ | 0.5MΩ | 1MΩ | ||||
| First effective measuring range | 1.51-200.0MΩ | 1.51-1000MΩ | 1.51-100.0MΩ | 1.51-200.0MΩ | 1.51-1000MΩ | |
| Accuracy | ±1.5%rdg±5dgt | ±1.5%rdg±5dgt | ||||
| Second effective measuring range | 0.00-1.50MΩ | 0.00-1.50MΩ | 1.20-1.50MΩ | 1.20-1.50MΩ | 1.20-1.50MΩ | |
| 200.1-2000MΩ | 1001-2000MΩ | 100.1-2000MΩ | 200.1-2000MΩ | 1001-2000MΩ | ||
| Accuracy | ±5.0%rdg±6dgt | |||||
| Open circuit voltage | 0 - +20% | |||||
| Short circuit current | Max 1.5mA | |||||
| Earth resistance | ||||||
| Measuring range(Auto range) | 20.00/200.0/2000Ω | |||||
| Accuracy | ±3.0%rdg±0.1Ω (20Ωrange) ±3.0%rdg±3dgt (200/2000Ωrange) | |||||
| Voltage measurement | ||||||
| Measuring range | AC 5-600V (45-65Hz) DC ±5-±1000V | |||||
| Accuracy | ±1.0%rdg±4dgt | |||||
| General | ||||||
| Applicable Standards | IEC 61010-1 CAT Ⅲ 600V, CAT IV 300V Pollution2 | |||||
| IEC 61010-2-030, IEC 61010-031(EMC), IEC 60529(IP54), IEC 61557-1,-2,-5,-10, IEC 61326-1,2-2, EN50581(RoHS) | ||||||
| Power source | LR6(AA)(1.5V) x 6 | |||||
| Dimensions / Weight | 84(L) x 184(W) x 133(D)mm / Approx. 900g (including batteries) | |||||
| Accessories | 7196A(Test leads with remote control switch), 7244A(Test lead with alligater clip), 8017(Extension prod), 8072(CAT II standard prod), 8212-USB(USB adaptor with "KEW Report (Software)"), 9155(Shoulder strap), 9156(Carrying case), LR6x6, Instruction manual | |||||
| Optional | 7243(L-shaped probe), 7245A(Precision measurement cord set), 8016(Hook type prod) | |||||
| Insulation Testing | |
|---|---|
| Test Voltage | 250V/50MΩ 500V/100MΩ 1000V/2000MΩ |
| Accuracy | ±5%rdg |
| Earth Resistance | |
| Simplified Precision measurement |
12Ω/120Ω/1200Ω |
| Accuracy | ±3% of full scale value |
| AC Voltage | |
| 0-600V AC | ±3% of full scale value |
| Earth Voltage | |
| 0-60V AC | ±3% of full scale value |
| Safety Standard | IEC 61010-1 CAT III 600V Pollution Degree 2 IEC 61010-2-031 IEC 61557 |
|---|---|
| Power source | LR6 (1.5V) × 8 |
| Dimensions | 130(L) × 183(W) × 100(D)mm |
| Weight | 1000g approx. |
| Included Accessories | 7103A (Test leads with remote control switch), 7131B (Safety crocodile clip [black]), 7161A (Flat test prod [black]) 8017 (Extension prod), 9092 (Cord case), 9121 (Shoulder strap), Battery LR6 (1.5V) × 8, Instruction Manual |
| Optional Accessories | 7100A (Precision measurement Cord Set) 7115(Extension prove) 8016(Hook type prod) |