Home  //  Products  //  Kyoritsu Indonesia
  • Email us at : sales@kyoritsuindonesia.com

KEW 6010B

Jual Multi Function Testers KEW 6010B

 

Multi Function Testers

KEW 6010B

KEW 6010B
CE
 
• Continuity:20/200Ω 200mA Test Current
• Insulation: 500/1000V, 20/200MΩ 1mA Rated Test Current
• Loop Impedance:20/2000Ω 15mA Test Current at 2000Ω (No RCD Trip)
• RCD:10/30/100/300/500mA x1/2, x1, Fast Trip(40ms), DC, Auto Ramp
• Test of a large kind of RCD's:Standard, Selective, AC and A(DC sensitive breakers)
• Uc(Contact Voltage): 100V
• Designed to IEC 61010-1, IEC 61557
• Data Memory:300 measured results
• The stored data can be transferred to PC via Optical Adaptor Model 8212-USB or 8212-RS232C.
 
Continuity Testing
Measuring Range 20/200Ω (Auto-Ranging)
Open Circuit Voltage > 6V
Short Circuit Current > 200mA
Accuracy ±(3%rdg + 3dgt)
Insulation Resistance Testing
Measuring Range 20/200MΩ (Auto-Ranging)
Test Voltage 500/1000V
Open Circuit Voltage +20% - 0%
Rated Current > 1mA
Accuracy ± (3%rdg + 3dgt)
Loop Impedance Testing
Impedance Range 20/2000Ω
Rated Voltage 230V + 10% - 15%(50Hz)
Normal Test Current 20Ω:25A/10ms
2000Ω:15mA/350ms max.
Accuracy ±(3%rdg + 8dgt)
RCD Testing
Test Current
(Test Current Duration)
x1/2, x1 10, 30, 100, 300, 500mA (2000ms)
Fast 150mA (50ms)
DC 10, 30, 100, 300mA (2000ms), 500mA (200ms)
Auto Ramp Goes up by 10% from 20% to 110% of IΔn. 300ms×10
Rated Voltage 230V + 10% - 15% 50Hz
AccuracyTest Current x1/2: -8%-2%
x1, FAST: +2%+8%
DC: ±10%
Auto Ramp: ±4%
Trip Time ±(1%rdg + 3dgt)
Uc Testing
Measuring Range 100V
Rated Voltage 230V + 10% - 15% (50Hz)
Test Current 5mA at IΔn = 10mA
15mA at IΔn = 30/100mA
150mA at IΔn = 300/500mA
Accuracy +5%+15%rdg, ±8dgt
Safety Standard IEC 61010-1 CAT III 300V Pollution Degree 2
IEC 61557-1, 2, 3, 4, 6, 10, IEC 60529 (IP40)
Power source R6 or LR6 × 8
Dimensions 175(L) × 115(W) × 86(D)mm
Weight 840g approx.
Included Accessories 7122B (Test leads)
KAMP10* (Test Lead with IEC Connector)
Pouch for Test leads
Shoulder Strap
Shoulder Pad
Instruction Manual
Optional Accessories 7133B (Distribution board test leads)
8212-RS232C (RS232C adaptor with "KEW Report (Software)")
8212-USB (USB adaptor with "KEW Report (Software)")

 

MODEL 6010A

Jual Multi Function Testers MODEL 6010A

 

Multi Function Testers

MODEL 6010A

MODEL 6010A
CE
 
Continuity and Insulation Testing
• Live circuit warning LED:
Immediate illumination of a warning lamp if the circuit under test is live
• Auto Discharge:
Allows fast and safe discharge of electrical energy stored in capacitive circuits following testing
• Integral overload protection on internal continuity and insulation test circuitry
• Autoranging
• 500V DC test voltage for insulation tests
• 200mA short circuit current on continuity ranges

Loop and RCD Testing
• Wiring connection check LED’s:
Immediate indication if wiring of circuit under test is correct
• Overheat Protection:
Rapid detection of overheating of internal circuitry,display of warning signal to user and automatic halting of measurement
• Supply Voltage Indication:
Can display supply voltage value in loop impedance mode
• Low Current Loop Impedance Test:
Short duration low test current will prevent tripping of many passive RCDs
• Auto Data Hold:
Retains displayed reading for set period following test
• Phase Angle Selection:
Selection of test current from +ve or -ve half cycle of waveform can prevent tripping of polarized type RCDs
 
Continuity Testing
Measuring Ranges 0 - 19.99 and 10.0 - 199.9Ω (2 auto ranges)
Open Circuit Voltage > 4V (as per IEC 364)
Short Circuit Current > 200mA DC (as per IEC 364)
Accuracy ±(3% + 3dgt)
Loop Impedance Testing
Rated Voltage 230V AC +10%-15% (50Hz)
Voltage Measuring Range 100-250V AC (50Hz)
Impedance Range
Nominal Test Current
20/2000Ω
25A (20Ω range) 15mA (2000Ω range)
Test Period 1/2 cycle (10ms)
Accuracy 20Ω range : ±(3% + 8dgt)   2000Ω range : ±(3% + 8dgt)
Insulation Testing
Measuring Ranges 0 - 19.99 and 10.0 - 199.9MΩ (2 auto ranges)
Test Voltage 500V DC
Output Voltage on
Open Circuit
570V DC±6%
Rated Current > 1mA (as per IEC 364)
Accuracy ± (3% + 3dgt)
RCD Testing
Rated Voltage 230V AC +10%-15% (50Hz)
Trip Current Settings RCD × 1/2: 5, 15, 50, 150, 250mA
RCD × 1: 10, 30, 100, 300, 500mA
Trip Current Duration RCD × 1/2 × 1: 2000ms
Fast Trip 150mA
Accuracy Trip current ±3% of test current at 230V.
Trip time ±(3% + 3dgt)
Safety Standard IEC 61010-1 CAT III 300V Pollution Degree 2
IEC 61010-2-031
IEC 61557
Power source R6 (AA) (1.5V) × 8
Dimensions 175(L) × 115(W) × 86(D)mm
Weight 780g approx.
Included Accessories 7122B (Test leads)
KAMP10* (Test Lead with IEC Connector)
Pouch for Test leads
Shoulder Strap
Shoulder Pad
R6 (AA) × 8
Instruction Manual
Optional Accessories 7133B (Distribution board test leads)

 

Multi Function Testers

Jual Multi Function Testers Kyoritsu

Multi Function Testers

  • MODEL 6010A

    MODEL 6010A

    Continuity and Insulation Testing
    • Live circuit warning LED:
    Immediate illumination of a warning lamp if the circuit under test is live
    • Auto Discharge:
    Allows fast and safe discharge of electrical energy stored in capacitive circuits following testing
    • Integral overload protection on internal continuity and insulation test circuitry
    • Autoranging
    • 500V DC test voltage for insulation tests
    • 200mA short circuit current on continuity ranges

    Loop and RCD Testing
    • Wiring connection check LED's:
    Immediate indication if wiring of circuit under test is correct
    • Overheat Protection:
    Rapid detection of overheating of internal circuitry,display of warning signal to user and automatic halting of measurement
    • Supply Voltage Indication:
    Can display supply voltage value in loop impedance mode
    • Low Current Loop Impedance Test:
    Short duration low test current will prevent tripping of many passive RCDs
    • Auto Data Hold:
    Retains displayed reading for set period following test
    • Phase Angle Selection:
    Selection of test current from +ve or -ve half cycle of waveform can prevent tripping of polarized type RCDs

    • KEW 6010B

      KEW 6010B

      • Continuity: 20/200Ω, 200mA Test Current
      • Insulation: 500/1000V, 20/200MΩ, 1mA Rated Test Current
      • Loop Impedance: 20/2000Ω, 15mA Test Current at 2000Ω (No RCD Trip)
      • RCD: 10/30/100/300/500mA x1/2, x1, Fast Trip(40ms), DC, Auto Ramp
      • Test of a large kind of RCD's:
      Standard, Selective, AC and A (DC sensitive breakers)
      • Uc (Contact Voltage): 100V
      • Designed to IEC 61010-1, IEC 61557
      • Data Memory: 300 measured results
      • The stored data can be transferred to PC via Optical Adaptor Model 8212-USB or 8212-RS232C.

      • MODEL 6011A

        MODEL 6011A

        • Complies with IEC 61557
        • Designed to IP 54 Rating
        • Live circuit and wiring connection check LED's
        • Triple ranges insulation tests at 250, 500 and 1000V
        • Triple range loop and PSC tests 15mA test current at 200Ω/2000Ω range (No RCD Trip)
        • Phase angle selection on RCD ranges
        • Polarity switch for continuity tests
        • Auto-null facility for continuity tests
        • Earth probe for loop impedance testing on extraneous metalwork
        • Contact Voltage Reading
        • Test of a large kind of RCD's:
        Standard, Selective, AC and A (DC sensitive breakers)

        • KEW 6016

          KEW 6016

          The KEW 6016 Multi-Function tester performs 10 functions
          in one instrument.

          • Continuity tester
          • Insulation resistance tester
          • Loop impedance tester
          • PSC tester
          • PFC tester
          • RCD tester
          • Earth tester
          • Phase rotation tester
          • Voltage measurement
          • Frequency measurement

          • MODEL 6018

            MODEL 6018

            • Designed to meet IEC 61010-1 CAT III 600V
            • Test leads with remote control switch.
            (For insulation&Simplified Earth Test)
            • Back light function.
            • Color coded scales and range switch position for easy reading.
            • Automatic warning when resistance of auxiliary earth spikes is in excess of tolerance.
            • Can be hung around the neck for both hand’s operation.

PV Insulation Earth Tester

KEW 6024PV

KEW 6024PVNEW

• Correct measuring for Insulation resistance even if the panel is under generating power
• Waterproof design: Can measure under the bad weather condition
• Memory function up to 1000 data
• Luminescence button and Backlight

  • Backlight USB AutoPowerOff