Home  //  Products  //  Clamp Meters  //  MODEL 2608A  //  Kyoritsu Indonesia
  • Email us at : sales@kyoritsuindonesia.com

RCD/LOOP/PAT Testers

Kyoritsu Indonesia

Jual RCD Testers Kyoritsu

RCD Testers

  • MODEL 5406A

    MODEL 5406A

    • Custom microprocessor controlled for highest accuracy and reliability.
    • 3 LEDs for checking correct wiring status.
    • 0 and 180 degree phase angle switch permits quick tests and consistent readings.
    • Digital read-out of tripping time.
    • Constant current source circuitry ensures that a fluctuating mains voltage does not affect the accuracy of readings.
    • Large custom digital display readout.
    • Visual indication of reversed phase and neutral wiring at socket.
    • Designed to IP54 Rating.
    • Complies with IEC 61557
    • Test of a large kind of RCD's: Standard, Selective, AC and A (DC sensitive breakers)

    • KEW 5410

      KEW 5410

      • Measurement of RCD trip time
      • Measurement of trip out current
      • Remote Test
      • Voltage Measurement
      • Auto-detection of Contact voltage
      • Dust- and Water-proof
      • Backlight

LOOP/PFC/PSC Testers</h3> <ul class="productList addOddEven"></h3> <ul class="productList addOddEven">
  • MODEL 4118A

    MODEL 4118A

    • Custom microprocessor controlled for highest accuracy and reliability.
    • 3 LEDs for checking correct wiring status.
    • 15mA LOOP measurement
    • Direct reading of Prospective Short Circuit Current (PSC).
    • Safe voltage measurement function.
    • Large custom digital display readout on all models.
    • Measure low loop resistances(resolution of 0.01Ω)
    • Automatic lock-out if test resister overheats.
    • Large custom digital display readout.
    • Visual indication of reversed phase and neutral wiring at socket.
    • Designed to IP54 Rating
    • Complies with IEC 61557

  • <li> <p class="img">

KEW 4140

KEW 4140

Anti-Trip Technology "ATT"
No RCDs tripping during Loop Testing!

Portable Appliance Testers

KEW 6201A

KEW 6201A

The KEW 6201A is a portable appliance tester, performing four functions to ensure the Safety of ClassI and ClassII appliances. And also can measure the mains voltage.
Readings are displayed on a large liquid crystal display (LCD) below which are four LEDs which unambiguously display a pass or fail indication for threshold values dictated by AS/NZS 3760.

 

KEW 6024PV

Jual PV Insulation Earth Tester KEW 6024PV

PV Insulation Earth Tester

KEW 6024PV NEW 

 

KEW 6024PV
CE
 
• Correct measuring for Insulation resistance even if the panel is under generating power
• Waterproof design: Can measure under the bad weather condition
• Memory function up to 1000 data
• Luminescence button and Backlight

Backlight USB AutoPowerOff

 

 

 

Insulation resistance PV insulationInsulation
            Test voltage 500V 1000V 250V  500V 1000V
Measuring range(Auto range) 20.00/200.0/2000MΩ 20.00/200.0/2000MΩ
Mid-scale value 50MΩ
Rated current 1.0-1.2mA
0.25MΩ 0.5MΩ 1MΩ
First effective measuring range 1.51-200.0MΩ 1.51-1000MΩ 1.51-100.0MΩ 1.51-200.0MΩ 1.51-1000MΩ
Accuracy ±1.5%rdg±5dgt ±1.5%rdg±5dgt
Second effective measuring range 0.00-1.50MΩ 0.00-1.50MΩ 1.20-1.50MΩ 1.20-1.50MΩ 1.20-1.50MΩ
200.1-2000MΩ 1001-2000MΩ 100.1-2000MΩ 200.1-2000MΩ 1001-2000MΩ
Accuracy ±5.0%rdg±6dgt
Open circuit voltage 0 - +20%
Short circuit current Max 1.5mA
Earth resistance      
 Measuring range(Auto range) 20.00/200.0/2000Ω
 Accuracy ±3.0%rdg±0.1Ω (20Ωrange) ±3.0%rdg±3dgt (200/2000Ωrange)
Voltage measurement      
 Measuring range AC 5-600V (45-65Hz) DC ±5-±1000V
 Accuracy ±1.0%rdg±4dgt
General      
 Applicable Standards IEC 61010-1 CAT Ⅲ 600V, CAT IV 300V Pollution2
  IEC 61010-2-030, IEC 61010-031(EMC), IEC 60529(IP54), IEC 61557-1,-2,-5,-10, IEC 61326-1,2-2, EN50581(RoHS)
 Power source LR6(AA)(1.5V) x 6
 Dimensions / Weight 84(L) x 184(W) x 133(D)mm / Approx. 900g (including batteries)
 Accessories 7196A(Test leads with remote control switch), 7244A(Test lead with alligater clip), 8017(Extension prod), 8072(CAT II standard prod), 8212-USB(USB adaptor with "KEW Report (Software)"), 9155(Shoulder strap), 9156(Carrying case), LR6x6, Instruction manual
 Optional 7243(L-shaped probe), 7245A(Precision measurement cord set), 8016(Hook type prod)

 

KEW 6016

Jual Multi Function Testers KEW 6016

 

Multi Function Testers

KEW 6016

KEW 6016
CE AutoDischarge ATT
 
Continuity Measurement
Continuous testing can be carried out by use of the test button lockdown feature. A selectable buzzer gives instantaneous indication of continuity. Null facility eliminates the test lead resistance from the results, the nulled value is retained even if the instrument is switched off. Live circuit warnings are given by a flashing LED, buzzer and indication on the display.

Insulation Measurement
Three selectable test voltages 250V, 500V and 1000V. An auto-discharge function ensures that circuits are not hazardous after testing. A red LED gives warning of high voltage output during testing and discharging of the circuit. In case of connecting to a live circuit, a live circuit warning is given by flashing LED, buzzer and indication on the display.

Loop Impedance Measurement
A patented (ATT) low current loop impedance test enables high accuracy loop measurements and quick testing without tripping RCD's.
A high current alternative is selectable for even higher accuracy and instantaneous results. The subsequent test will default to the low current test, this saves any inadvertent tripping of the RCD. The KEW 6016 allows also for phase to phase loop tests.

PSC / PFC Measurement
The Prospective Short Circuit Current (PSC) and Prospective Fault Current (PFC) are automatically calculated and shown on the display. As loop testing, the function has low and high test current options with the default to low current to avoid inadvertent tripping of RCDs.

RCD Measurement
The KEW 6016 has a comprehensive RCD test feature for RCD type AC (Alternative Currents), RCD type A (Pulsating Direct Currents), General and Selective (delayed).

Measures at 1/2x, 1x, 5x of nominal RCD current. It also has Ramp Test and Auto test where all results are shown on one screen. Touch voltage limit can be selected for 25V or 50V depending on application.

Earth Measurement
Using the classical Volt-Amper method with two auxiliary earth spikes and without external power source. All test leads and spikes are supplied as standard accessories.

Phase rotation
KEW 6016 can check the phase rotation of three phase lines with clear indication of the sequence on the display.

Voltage Measurement
In addiction to the voltage measurement, this function gives also the Frequency of the voltage under test.

Continuity
Range 20/200/2000Ω (Auto-ranging)
 Open circuit
voltage (DC)
5V±20% (*1)
Short circuit
current
Greater than 200mA
Accuracy  ±0.1Ω (0 - 0.19Ω)
±2%rdg+8dgt (0.2 - 2000Ω) 
Insulation Resistance
Range 20/200MΩ
(Auto-ranging)
20/200/2000MΩ (Auto-ranging)
Open circuit
voltage (DC)
250V+25% -0% 500V+25% -0% 1000V+20% -0%
Rated current 1mA or greater
@ 250kΩ 
1mA or greater
@ 500kΩ
1mA or greater
@ 1MΩ
Accuracy ±2%rdg+6dgt
(0 - 19.99MΩ)
±5%rdg+6dgt
(20 - 200MΩ)
±2%rdg+6dgt (0 - 199.9MΩ)
±5%rdg+6dgt (200 - 2000MΩ)
Loop Impedance
Function L-PE L-PE (ATT) L-N / L-L
Rated Voltage 100 - 260V 50/60Hz L-N: 100 - 300V
L-L: 300 - 500V
50/60Hz
Nominal Test
Current at 0Ω
External Loop:
Magnitude/
Duration (*2)
20Ω: 6A/20ms
200Ω: 2A/20ms
2000Ω: 15mA/500ms
L-N: 6A/60ms
N-PE: 10mA/approx. 5s
20Ω: 6A/20ms
Range 20/200/2000Ω
(Auto-ranging)
20/200/2000Ω
(Auto-ranging)
(L-N < 20Ω)
20Ω
Accuracy ±3%rdg+4dgt(*3)
±3%rdg+8dgt(*4)
±3%rdg+6dgt (*3)
±3%rdg+8dgt(*4)
±3%rdg+4dgt (*3)
±3%rdg+8dgt(*4)  
PSC (L-N / L-L) / PFC (L-PE)
Function PSC PFC PFC (ATT)
Rated Voltage 100 - 500V 50/60Hz 100 - 260V 50/60Hz  
Nominal Test
Current at 0Ω
External Loop:
Magnitude/
Duration (*5)
6A/20ms 6A/20ms
2A/20ms
15mA/500ms
L-N: 6A/60ms
N-PE: 10mA/approx. 5s 
 Range 2000A/20kA Auto-Ranging
Accuracy PSC / PFC accuracy is derived from measured loop impedance
specification and measured voltage specification
RCD
Function X1/2 X1 X5 Ramp Auto
Trip current
setting
10/30/100/300/
500/1000mA
10/30/
100mA   
10/30/
100/300/
500mA
Depending on the
accuracy at each
function.
Measurement sequence:
X1/2 0°→X1/2 180°
→X1 0°→X1 180°
→X5 0°→X5 180°
Measurements with
x5 are not carried out
for RCDs with
nominal current of
100mA or more.
Trip current
Duration
2000ms G: 550ms
S: 1000ms
410ms Goes up by
10% from
20% to
110%
G:300ms/
S:500ms
X10 times
Rated Voltage 230V+10%-15% 50/60Hz
Accuracy AC Type:
-8% - -2%
A Type:
-10% - 0%
AC Type: +2% - +8%
A Type: 0% - +10%
AC Type: ±4%
A Type: ±10%
Trip time: ±1%rdg+3dgt
RCD (Uc)
Function UC
Rated Voltage 230V+10% - 15% 50/60Hz
Range 100.0V
Test current ≤ 1/2IΔn (max150mA)
Accuracy +5% - +15%rdg, ±8dgt
Earth
Range 20/200/2000Ω Auto-Ranging
Accuracy 20Ω: ±3%rdg+0.1Ω
200/2000Ω: ±3%rdg+3dgt (Auxiliary earth resistance 100±5%)
Phase Rotation
Rated Voltage 50-500V 50/60Hz
Remarks Correct phase sequence: are displayed "1.2.3" and  recycle mark
Reversed phase sequence: are displayed "3.2.1" and  recycle mark
Volts
Function Volts Frequency
Rated Voltage 25 - 500V, 45 - 65Hz
Measuring range  25 - 500V 45 - 65Hz
Accuracy ±2%rdg+4dgt ±0.5%rdg+2dgt
Applicable standards IEC 61010-1 CAT III 300V (500V L to L) Pollution degree 2, IEC 61010-031,
IEC 61557-1, 2, 3, 4, 5, 6, 7, 10, IEC 60529 (IP40), IEC 61326 (EMC)
Power source LR6 X 8
Dimensions 136(L) X 235(W) X 114(D)mm
Weight 1350g (including batteries.)
Included Accessories 7188A (Distribution board fuse test lead set)
7196A (Test leads with remote control switch)
7218A (Power cord [EU]) (*6)
7228A (Earth resistance test leads)
8032 (Auxiliary earth spikes)
8212-USB (USB adaptor with KEW Report (Software))
9142 (Carrying case)
9121 (Shoulder strap)
Cord case, Buckle, Battery, Instruction manual
Optional Accessories 8212-RS232C (RS232C adaptor with KEW Report (Software))

 

MODEL 6018

Jual Multi Function Testers MODEL 6018

 

Multi Function Testers

MODEL 6018

MODEL 6018
CE AutoDischarge
 
• Designed to meet IEC 61010-1 CAT III 600V
• Test leads with remote control switch.
(For insulation&Simplified Earth Test)
• Back light function.
• Color coded scales and range switch position for easy reading.
• Automatic warning when resistance of auxiliary earth spikes is in excess of tolerance.
• Can be hung around the neck for both hand’s operation.
 
Insulation Testing
Test Voltage 250V/50MΩ
500V/100MΩ
1000V/2000MΩ
Accuracy ±5%rdg
Earth Resistance
Simplified Precision
measurement
12Ω/120Ω/1200Ω
Accuracy ±3% of full scale value
AC Voltage
0-600V AC ±3% of full scale value
Earth Voltage
0-60V AC ±3% of full scale value
Safety Standard IEC 61010-1 CAT III 600V Pollution Degree 2
IEC 61010-2-031
IEC 61557
Power source LR6 (1.5V) × 8
Dimensions 130(L) × 183(W) × 100(D)mm
Weight 1000g approx.
Included Accessories 7103A (Test leads with remote control switch),
7131B (Safety crocodile clip [black]), 7161A (Flat test prod [black])
8017 (Extension prod), 9092 (Cord case), 9121 (Shoulder strap),
Battery LR6 (1.5V) × 8, Instruction Manual
Optional Accessories 7100A (Precision measurement Cord Set)
7115(Extension prove)
8016(Hook type prod)

 

MODEL 6011A

Jual Multi Function Testers MODEL 6011A

 

Multi Function Testers

MODEL 6011A

MODEL 6011A
CE
 
• Complies with IEC 61557
• Designed to IP 54 Rating
• Live circuit and wiring connection check LED's
• Triple ranges insulation tests at 250, 500 and 1000V
• Triple range loop and PSC tests 15mA test current at 200Ω/2000Ω range(No RCD Trip)
• Phase angle selection on RCD ranges
• Polarity switch for continuity tests
• Auto-null facility for continuity tests
• Earth probe for loop impedance testing on extraneous metalwork
• Contact Voltage Reading
• Test of a large kind of RCD's: Standard, Selective, AC and A
(DC sensitive breakers)
 
Continuity Testing
Measuring Ranges 20/200/2000Ω (Autoranging)
Open Circuit Voltage >6V
Short Circuit Current >200mA DC
Accuracy ±(1.5%rdg+3dgt)
Insulation Testing
Measuring Ranges 20/200MΩ (Autoranging)
Test Voltage 250V 500V 1000V DC
Output Voltage on Open Circuit 250V+40%-0%
500V+30%-0%
1000V+20%-0%
Rated Current > 1mA
Accuracy ±(1.5%rdg+3dgt)
Loop Impedance Testing
Rated Voltage 230V AC +10%-15% [50Hz]
Voltage Measuring Range 100 - 250V AC [50Hz]
Impedance Ranges 20/200/2000Ω
Nominal Test Current 25A (20Ω range) 15mA (200Ω range) 15mA (2000Ω range)
Accuracy 20Ω range ±(3%rdg +4dgt)
200Ω range ±(3%rdg +8dgt)
2000Ω range ±(3%rdg +4dgt)
PSC Testing
Rated Voltage 230V AC +10%-15% [50Hz]
PSC Ranges 200A (15mA Test Current)
2000A (25A Test Current)
20kA (25A Test Current)
Accuracy PSC accuracy derived from measured loop impedance specification
and measured voltage specification
RCD Testing
Rated Voltage 230V AC +10%-15% [50Hz]
Trip Current Settings RCD × 1/2 : 10,30,100,300,500,1000mA
RCD × 1 : 10,30,100,300,500,1000mA
RCD × 5 : 10,30,100,300mA (on × 5 ranges max current 1A)
Trip Current Duration RCD × 1/2 × 1: 2000ms
RCD fast: 50ms
Accuracy Trip current +10%-0% of test current at 230V
Trip time ±(1%rdg + 3dgt)
Safety Standard IEC 61010-1 CAT III 300V Pollution Degree 2
IEC 61557
Power source LR6 (1.5V) × 8
Dimensions 130(L) × 183(W) × 100(D)mm
Weight 1100g approx.
Included Accessories *KAPM10
(Molded plug test leads for loop and RCD testing at sockets)
7122B (Test leads)
7132A (External earth probe)
Pouch for Test Leads
9121 (Shoulder Strap)
Battery LR6 (1.5V) × 8
Instruction Manual
Optional Accessories 7133B (Distribution board test leads)

 

206263
Today
Yesterday
This Week
Last Week
This Month
Last Month
All days
117
115
232
205067
1873
5007
206263

Your IP: 3.227.249.234
Server Time: 2019-10-14 19:22:25